机房温湿度:ASHRAE TC9.9 推荐区间与允许区间
- 推荐区间(A1–A4 类设备):进风干球温度 18–27℃,露点不高于 15℃、相对湿度不高于 60%。
- 允许区间按设备等级放宽:A1 为 15–32℃、相对湿度上限 80%,A4 可到 5–45℃。
- 推荐区间是建议而非强制,适当提高送风温度、延长自然冷却时间是降低 PUE 的常用做法。
Technical articles
All typesTechnical analysis 72Incident reviews 8Field experience 31Standards 5Equipment and technology 81Trend research 69
All countriesUnited States 152China 86Germany 4United Kingdom 3France 2Italy 2Canada 2Singapore 2Japan 2Denmark 1India 1Norway 1Netherlands 1South Korea 1罗马尼亚 1
- 2026-10-20暖通与制冷Incident reviewsNorway
挪威数据中心因冷却液反复泄漏与变压器火灾导致投产延误
- 管道密封剂故障和过滤器问题致冷却液反复泄漏,频繁导致停电、排查补漏与重注液调试,最终迫使现场于6月整体更换冷却系统。
- 系统整换后9月又因人为失误发生重大泄漏,暴露施工运维管控漏洞。
- 变压器火灾导致开关设备烧毁并产生10项安全违规,现场启用临时发电机紧急维持冷却运行以避免服务器断冷。
SourcesIDC 圈·云与算力cloud.idcquan.com - 2023-11-09暖通与制冷Incident reviewsSingapore
新加坡两银行数据中心冷冻水系统故障致业务中断近14小时
- 数据中心因冷冻水系统发生故障,导致机房内温度急剧升高影响服务器运行,故障从下午持续至次日凌晨近14个小时。
- 两家银行启动灾备计划向备用数据中心切换,但因技术问题均未能成功恢复系统运行,暴露出灾备切换演练与可用性问题。
Sources中国IDC圈·安全监控dc.idcquan.com - 2020-03-30暖通与制冷Incident reviewsChina
冷机冷却水自清洗过滤器漏水应急抢修与非全尺寸备件管理
- DN350自清洗过滤器因水封腐蚀且钢刷主轴磨损导致冷却水泄漏、冷机停机,由于备用冷机故障无法启动,制冷系统面临无冗余运行风险。
- 针对异型主轴制作需3至4天的问题,抢修组拆除主轴与内刷,用铁板焊死法兰盘安装孔后回装,耗时2.5小时完成盲堵注水,恢复N+1冗余。
- 提出储备功能降级但体积小、安装快的“非全尺寸”应急备件,通过临时牺牲自动排污清洗等次要功能,缩短抢修时间并降低库房占用。