- 2018-12-07暖通与制冷Field experienceChina
UPS机房制冷气流组织要点与失冷极限温升测试流程
- UPS设备多为中部进风、上出风,空调安装需避免直吹配电柜以防高湿结露,并防止距UPS过近导致中部进风受阻。
- 验收时建议通过假负载满载进行极限温升测试:冷通道控制在18℃~27℃后关闭制冷,每隔半分钟或一分钟记录温升。
- 冷通道达到极限温度后开启制冷并记录降温恢复耗时,以此摸清机房失冷缓冲时间并制定应急响应时间标准。
Sources中国IDC圈·空调制冷dc.idcquan.com - 2018-10-09暖通与制冷Technical analysisChina
液冷与自然水冷在数据中心的应用模式及典型案例
- 北大未名一号采用45℃温水水冷技术,通过无泄漏快速连接系统直接冷却核心处理器及内存,PUE达到1.1,计算效率达92.6%。
- 阿里千岛湖数据中心利用深层密闭管道湖水换热制冷,年均PUE低于1.3;挪威绿山数据中心则利用峡湾8℃冷水循环实现全年自然冷却。
- Google芬兰项目通过板式换热器使内循环淡水与外循环海水隔离换热,升温后的海水先经混合调温后再排入海洋,实现完全无冷机的海水自然散热。
Sources中国IDC圈·空调制冷dc.idcquan.com - 2018-09-11暖通与制冷Field experienceChina
数据中心机房精密空调常见报警分析与日常维护方法
- 低电源电压或缺相会导致24V变压器输出不足、冷凝器交流接触器无法吸合,需用万用表排查判定并可配设稳压器。
- 高压控制器一般调定在350psig,超限触发报警后需手动复位,通常由氟利昂压力过高/过低导致压机过热引起,需用压力表检测排查。
- 加湿器平底锅易聚集矿物沉积物需定期拆卸清洗;清洗冷凝器积尘时切忌损伤铜管和翅片,维护后在系统菜单确认即可消除维护告警。
Sources中国IDC圈·空调制冷dc.idcquan.com