- 2024-09-18消防与安全Incident reviewsSingapore
阿里云新加坡机房锂电池爆炸火灾复盘及灭火应对分析
- 机房起火原因为锂电池爆炸,现场出动水枪、室内自动喷水及灭火机器人冷却,火灾持续超过33小时仍难以完全扑灭。
- 因消防持续浇水导致机房出现积水与渗漏,存在电路短路风险,现场被迫对整个可用区C单栋机房大楼执行紧急切电。
- 锂电池火灾需兼顾快速灭火与持续冷却降温,全氟己酮能快速汽化吸热并隔绝氧气,而水介质灭火需警惕引发电池短路及剧烈化学反应。
Sources中国IDC圈·安全监控dc.idcquan.com - 2024-09-18消防与安全Incident reviewsChina
从阿里云新加坡机房火灾看数据中心锂电池室消防设计规范
- 分析认为新加坡机房火灾难灭主因在于锂电室消防设计欠缺,未落实事故通风、电池间消防排水及非消防一键紧急切断等措施,导致灭火持续浇水时出现积水渗漏和短路风险。
- 电池选型方面,三元锂热失控会自身产生氧气加剧燃烧,而磷酸铁锂相对更安全;针对锂电火灾,水消防在控火和持续降温抑制复燃方面是目前公认最有效的方式。
- 规范要求锂电池房洒水启动后需快速切断电路,并配置事故通风以防止锂电池着火释放的大量烟雾导致其他房间设备短路。
Sources中国IDC圈·运维管理dc.idcquan.com