    机房温湿度:ASHRAE TC9.9 推荐区间与允许区间

    • 推荐区间(A1–A4 类设备):进风干球温度 18–27℃,露点不高于 15℃、相对湿度不高于 60%。
    • 允许区间按设备等级放宽:A1 为 15–32℃、相对湿度上限 80%,A4 可到 5–45℃。
    • 推荐区间是建议而非强制,适当提高送风温度、延长自然冷却时间是降低 PUE 的常用做法。

Technical articles

  • 2026-10-11暖通与制冷Equipment and technologyJapan

    三菱重工推出面向数据中心等余热回收的高温离心式热泵

    • ETI-W系列热泵采用HFO1233zd(E)冷媒,最大制热量达640kW,可回收冷水机组冷却水余热制备高达90℃的高温热水。
    • 该设备在制取90℃热水的高温出水工况下,制热能效比(COP)仍可达到4.01,可用于数据中心余热再利用及区域供暖。