- 2024-09-18消防与安全Incident reviewsSingapore
阿里云新加坡机房锂电池爆炸火灾复盘及灭火应对分析
- 机房起火原因为锂电池爆炸,现场出动水枪、室内自动喷水及灭火机器人冷却,火灾持续超过33小时仍难以完全扑灭。
- 因消防持续浇水导致机房出现积水与渗漏,存在电路短路风险,现场被迫对整个可用区C单栋机房大楼执行紧急切电。
- 锂电池火灾需兼顾快速灭火与持续冷却降温,全氟己酮能快速汽化吸热并隔绝氧气,而水介质灭火需警惕引发电池短路及剧烈化学反应。