    机房温湿度:ASHRAE TC9.9 推荐区间与允许区间

    • 推荐区间(A1–A4 类设备):进风干球温度 18–27℃,露点不高于 15℃、相对湿度不高于 60%。
    • 允许区间按设备等级放宽:A1 为 15–32℃、相对湿度上限 80%,A4 可到 5–45℃。
    • 推荐区间是建议而非强制,适当提高送风温度、延长自然冷却时间是降低 PUE 的常用做法。