M&E operations
This page's content is in Chinese.
Data center power, cooling, water and fire: power distribution, cooling, environment monitoring, fire safety and operations
3 articles · Collected every 30 minutes from trade media and news
All directionsPower distribution 86HVAC and cooling 101Environment monitoring 7Fire and safety 8Facilities and infrastructure 47Operations 14
Basics
- OperationsChina
PUE 与能效等级:GB 40879-2021
- PUE = 数据中心总耗电 ÷ IT 设备耗电,越接近 1 越好;国际上的定义见 ISO/IEC 30134-2。
- GB 40879-2021 把数据中心能效分为三级:1 级 PUE ≤ 1.20、2 级 ≤ 1.30、3 级 ≤ 1.50,3 级即能效限定值。
- 标准 2021 年 10 月发布,2022 年 11 月 1 日起实施,是强制性国家标准。
Technical articles
All typesTechnical analysis 71Incident reviews 8Field experience 31Standards 5Equipment and technology 79Trend research 69
All countriesUnited States 150China 85Germany 4United Kingdom 3France 2Italy 2Canada 2Singapore 2Japan 2Denmark 1India 1Norway 1Netherlands 1South Korea 1罗马尼亚 1
- 2022-11-24运维管理Field experienceChina
数据中心机房搬迁关键步骤与全流程运维管控要点
- 搬迁前需全面评估承接机房的供电、制冷及空间,提前完成综合布线与网络互联测试,并规划机柜、网络与配电设备的摆放与搬运流线。
- 硬件迁移需严格执行停机流程,确认数据备份成功并完全断电断网后方可拆机,设备拆装运输需采用专业防震包装并执行逐级清点标识。
- 设备入位后需复测电力供给与网络稳定性,搬迁后重新盘点建立运维表单,淘汰硬盘等介质需经反复覆写或物理销毁以保障数据安全。
Sources中国IDC圈·运维管理dc.idcquan.com - 2021-08-03运维管理Field experienceChina
数据中心运维人员工时量化配置、三级巡检机制及智能化实践探讨
- 腾讯通过量化工时配置运维人员,统计设备类型、数量、维保频次及耗时计算总工时,再与工程师可用工时对比分析以合理排班。
- 汇天网络推行三类巡检机制:一线巡检排查明显设备问题,二线进行预测性推断,运维专家及经理复核托管设备变更与公共区新增物品。
- 业内专家指出智能巡检机器人因成本高且机房环境非标准化,目前多局限于简单巡查,尚无法替代人工完成复杂运维操作。
Sources中国IDC圈·运维管理dc.idcquan.com - 2018-05-08运维管理Field experienceChina
数据中心在线状态监测与降低人为误操作的运维管理实践
- 设备状态监测:利用差压传感器与BMS联动监测过滤器,对关键设备部署加速度计进行在线振动分析、趋势归档和阈值报警。
- 操作规范化:建立逐步清单并实施双人见证复核;操作程序中需明确每一步的预期物理结果(如水泵启停压力流量、断路器指示灯等)。
- 人员培训与审计:人为错误导致70%至80%的设施问题;需通过培训考核认证后独立上岗,并结合随机突击审计排查管理盲区。
Sources中国IDC圈·安全监控dc.idcquan.com
Articles are automatically picked from trade media and data center news, then categorized with Chinese key points. Check the original for technical parameters. If you spot a problem, pleaseFeedback。