Data center power, cooling, water and fire: power distribution, cooling, environment monitoring, fire safety and operations
2 articles · Collected every 30 minutes from trade media and news
All directionsPower distribution 86HVAC and cooling 104Environment monitoring 7Fire and safety 8Facilities and infrastructure 47Operations 14
Basics
- OperationsChina
PUE 与能效等级:GB 40879-2021
- PUE = 数据中心总耗电 ÷ IT 设备耗电,越接近 1 越好;国际上的定义见 ISO/IEC 30134-2。
- GB 40879-2021 把数据中心能效分为三级:1 级 PUE ≤ 1.20、2 级 ≤ 1.30、3 级 ≤ 1.50,3 级即能效限定值。
- 标准 2021 年 10 月发布,2022 年 11 月 1 日起实施,是强制性国家标准。
Technical articles
All typesTechnical analysis 72Incident reviews 8Field experience 31Standards 5Equipment and technology 81Trend research 69
All countriesUnited States 152China 86Germany 4United Kingdom 3France 2Italy 2Canada 2Singapore 2Japan 2Denmark 1India 1Norway 1Netherlands 1South Korea 1罗马尼亚 1
- 2022-12-02运维管理Technical analysisChina
数据中心常见机电故障成因剖析与高密极端环境应对
- 电线绝缘层正常寿命10-20年,长期高负荷运行产热会加速击穿引发短路;铅酸与锂电池临期若未及时更换,接头松动或内短路极易诱发热失控起火蔓延。
- 高密机柜导致冷却故障后的应急窗口严重压缩,机房5分钟可升温3-5℃、20分钟升温15-20℃,排障处置时间由原本的30分钟压缩至10分钟以内。
- 超大园区单体测点达10万以上,需依赖DCIM强化巡检;同时需应对极端气候变数,打破传统设计边界并针对性储备防汛与柴发长周期运行保障物资。
Sources中国IDC圈·安全监控dc.idcquan.com - 2022-10-14运维管理Technical analysisChina
数据中心巡检机器人替代人工可行性与运维场景分析
- 机器人能替代重复性读数核对及蓄电池表面测温等标准化检查,但在复杂环境与痕迹判断上传感器精度不足,易出现误判漏判。
- 不同冷机、水泵在各工况下的声音指标缺乏标准化分类数据,且机房环境嘈杂,机器人听觉分析和异响识别现阶段难以落地。
- 平台调优机器人响应更快,但分合闸、并机切换及EOP类应急硬件操作出于安全考虑仍必须人工现场执行,机器人目前仅适合作为辅助。
Sources中国IDC圈·运维管理dc.idcquan.com