M&E operations
This page's content is in Chinese.
Data center power, cooling, water and fire: power distribution, cooling, environment monitoring, fire safety and operations
2 articles · Collected every 30 minutes from trade media and news
All directionsPower distribution 86HVAC and cooling 100Environment monitoring 7Fire and safety 8Facilities and infrastructure 47Operations 14
Basics
Technical articles
All typesTechnical analysis 71Incident reviews 8Field experience 31Standards 5Equipment and technology 78Trend research 69
All countriesUnited States 149China 85Germany 4United Kingdom 3France 2Italy 2Canada 2Singapore 2Japan 2Denmark 1India 1Norway 1Netherlands 1South Korea 1罗马尼亚 1
- 2026-05-12消防与安全Equipment and technologyChina
双登液冷储能集装箱完成极限火烧测试与热蔓延阻隔验证
- 在100% SOC且关闭主动消防干预下历经8小时明火燃烧,燃烧舱内最高温达1269℃,相邻储能箱电池模组仅90℃,实现零爆炸、零串燃、零塌舱。
- 模组采用耐1300℃以上的多层复合隔热结构切断传热,系统级采用A60级防火防爆舱体结合定向泄爆通道,实现快速释放高压高热且舱体不变形。
- 系统通过UL9540A与NFPA855标准测试,结合AI多维传感阵列监测温、烟、气体和压力,电芯在150℃下保持结构稳定以抑制热失控。
Sources中国IDC圈·模块化dc.idcquan.com - 2024-09-18消防与安全Incident reviewsChina
从阿里云新加坡机房火灾看数据中心锂电池室消防设计规范
- 分析认为新加坡机房火灾难灭主因在于锂电室消防设计欠缺,未落实事故通风、电池间消防排水及非消防一键紧急切断等措施,导致灭火持续浇水时出现积水渗漏和短路风险。
- 电池选型方面,三元锂热失控会自身产生氧气加剧燃烧,而磷酸铁锂相对更安全;针对锂电火灾,水消防在控火和持续降温抑制复燃方面是目前公认最有效的方式。
- 规范要求锂电池房洒水启动后需快速切断电路,并配置事故通风以防止锂电池着火释放的大量烟雾导致其他房间设备短路。
Sources中国IDC圈·运维管理dc.idcquan.com
Articles are automatically picked from trade media and data center news, then categorized with Chinese key points. Check the original for technical parameters. If you spot a problem, pleaseFeedback。