- HVAC and coolingUnited States
机房温湿度:ASHRAE TC9.9 推荐区间与允许区间
- 推荐区间(A1–A4 类设备):进风干球温度 18–27℃,露点不高于 15℃、相对湿度不高于 60%。
- 允许区间按设备等级放宽:A1 为 15–32℃、相对湿度上限 80%,A4 可到 5–45℃。
- 推荐区间是建议而非强制,适当提高送风温度、延长自然冷却时间是降低 PUE 的常用做法。
Technical articles
All typesTechnical analysis 71Incident reviews 8Field experience 31Standards 5Equipment and technology 79Trend research 69
All countriesUnited States 150China 85Germany 4United Kingdom 3France 2Italy 2Canada 2Singapore 2Japan 2Denmark 1India 1Norway 1Netherlands 1South Korea 1罗马尼亚 1
- 2020-03-30暖通与制冷Incident reviewsChina
冷机冷却水自清洗过滤器漏水应急抢修与非全尺寸备件管理
- DN350自清洗过滤器因水封腐蚀且钢刷主轴磨损导致冷却水泄漏、冷机停机,由于备用冷机故障无法启动,制冷系统面临无冗余运行风险。
- 针对异型主轴制作需3至4天的问题,抢修组拆除主轴与内刷,用铁板焊死法兰盘安装孔后回装,耗时2.5小时完成盲堵注水,恢复N+1冗余。
- 提出储备功能降级但体积小、安装快的“非全尺寸”应急备件,通过临时牺牲自动排污清洗等次要功能,缩短抢修时间并降低库房占用。